The Ecowec XF10 AISI316 is a specially reinforced heat exchanger that operates on the forced counterflow principle for the heat recovery of industrial process liquids.
A value-added tax of 24% is added to the price.
The Ecowec® XF10 AISI316 is a reinforced pressure class PN6 heat exchanger that operates on the forced counterflow principle for the heat recovery of industrial process liquids.
It is designed for industrial plants and processes, laundries, hospitals, and other properties where significant amounts of energy are wasted without capturing the heat from them.
Flow rates: Maximum flow rate for primary and secondary sides 100 l/s, maximum temperature of flowing liquids 85°C.
Connection Recommendation: Requires pressurized wastewater guidance to the exchanger using a wastewater pumping station, and connection to the heat pump. Heat recovery can be enhanced by connecting multiple hybrid exchangers in series and/or in parallel within the same system.
Dimensions: Width 950 mm, Height 2000 – 2300 mm, Weight 600 kg (empty), 1,600 kg (in use).
Application Areas: wastewater, pool water, steam, condensates, process fluids.
Pressure class: PN6
Connection: 4 pcs of DN100 flanges for primary and secondary fluids
Wastewater heat recovery is the most cost-effective way to reduce the property’s energy consumption. About 30% of the residential building’s annual heating energy consumption goes to heating the domestic water and thereby to the sewer. In energy-efficient class A properties, the share of energy contained in domestic water is more than 50% of the heat balance. It is possible to recover thermal energy from waste water sent to the sewer and use it again with the help of the Ecowec hybrid exchanger.